• New
Three-phase outdoor unit AJY072LELDH for Fujitsu Airstage VRF system, J-IVL Series

Three-phase outdoor unit AJY072LELDH for Fujitsu Airstage VRF system, J-IVL Series

  • Cooling Capacity: 22.4 kW
  • Heating Capacity: 22.4 kW
  • Maximum connectable indoor units: 1-20
  • Maximum pipe lenght: 400 m
  • Maximum height difference (upper/lower): 50/40 m
  • Operating Range:
    • Cooling: -15 to 46°C
    • Heating: -20 to 21°C

 
Technical Specifications of three-phase outdoor unit AJY072LELDH for Fujitsu Airstage VRF system, J-IVL Series
Rated capacity range HP 8
Model name AJY072LELDH
Maximum connectable indoor units 1-20
Power source 3-phase, 400V~, 50Hz
Capacity Cooling kW 22.4
Nominal Heating 22.4
Max. Heating 25.0
Input power Cooling kW 6.30
Nominal Heating 4.65
Max. Heating 5.45
EER Cooling W/W 3.56
COP Nominal Heating 4.82
Max. Heating 4.56
SEER Cooling 7.62
SCOP Heating 3.89
ηc Cooling % 301.8
ηh Heating 152.6
Air flow rate High m3/h 8,400
Sound pressure level/
Power level
Cooling % 52 / 66
Heating 54 / 66
Heat exchanger fin Blue fin
Net Dimensions Height mm 1,428
Width 1,080
Depth 480
Weight kg 170
Refrigerant Type (Global Warming Potential) R410A (2,088)
Charge kg (CO2eq-T) 7.0 (14.6)
Connection pipe diameter Liquid mm 9.52
Gas 19.05
Total pipe length m 400
Max. height difference 50/40 (Outdoor unit: Upper/Lower)
Operating Range Cooling °CDB -15 to 46
Heating -20 to 21

Note: Specifications are based on the following conditions.
Cooling: Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB.
Heating: Indoor temperature of 20°CDB/(15°CWB), and outdoor temperature of 7°CDB/6°CWB.
Pipe length: 7.5 m; Height difference between outdoor unit and indoor unit: 0 m.
The protective function may work when using it outside the operation range.

Manufacturer Fujitsu Airstage
Series J-IVL
Outdoor Unit AJY072GALDH
Power supply (V/ø/Hz) 400 / 3 / 50
Cooling Capacity (kW) 22.4
Heating Capacity (kW) 22.4
EER (Energy Efficiency in Cooling) 3.56
COP (Energy Efficiency in Heating) 4.82
SEER (Seasonal Cooling Efficiency) 7.62
SCOP (Seasonal Heating Efficiency) 3.89
Sound Pressure Outdoor Unit - Cooling/Heating dB(A) 52 / 54
Sound Power Outdoor Unit - Cooling/Heating dB(A) 66 / 66
Dimensions - Outdoor Unit WxHxD (mm) 1,080 x 1,428 x 480
Weight - Outdoor Unit (kg) 170
Maximum Pipe Lenght (m) 400
Maximum Height Difference (m) 50 / 40
Operation Range - Cooling (°C) -15 ~ 46
Operation Range - Heating (°C) -20 ~ 21
Refrigerant (type) R410A
No reviews
Product added to compare.