Ceiling-floor type fan coil Midea MKH2-V500-R4

Ceiling-floor type fan coil Midea MKH2-V500-R4

  • Cooling
    4.85 kW
  • Heating
    5.25 kW
  • Noise
    43 dB

 

Features:

  • 3 or 4 rows coil are optional for whole series.
  • 2-Pipe and 4-Pipe are optional for whole series.
  • Ultra-thin with 200 mm thickness.
  • Hysteresis temperature can be set in heating and cooling mode by PCB switch, field adjustable.
  • With/without forced fan on can be set by PCB switch, field adjustable.
  • The XYE port(Centralized) and PQE port (Modbus) are can be customized.
  • 0-1 OV fan speed control port is optional.
  • Floor standing/Horizontal/ Concealed type installation available (For floor standing : The footing is optional).
  • Auto mode and 7 fan speed (by 75A wired controller).
Technical Specifications for Midea MKH2-V500-R4 Fan coil
Model

MKH2-V500-R4

Power supplyV/Ph/Hz220-240 / 1 / 50
Air flow (H/M/L)m3/h800 / 600 / 420
CFM471 / 353 / 247
Cooling1Capacity (H/M/L)kW4.85 / 3.92 / 2.93
Water flow rate (H/M/L)m3/h0.83 / 0.67 / 0.51
Water pressure dropkPa54.3 / 36.81 / 21.77
Heating2Capacity (H/M/L)kW5.25 / 4.09 / 3.04
Water flow rate (H/M/L)m3/h0.91 / 0.71 / 0.53
Water pressure dropkPa53.4 / 36.54 / 20.47
Power input (H/M/L)W52 / 28 / 15
Sound power level (H/M/L)dB(A)59 / 51 / 43
Fan motorTypeLow noise DC fan motor
Quantity1
FanTypeCentrifugal, forward-curved Blades
Quantity2
CoilRow4
Max. working pressureMPa1.6
Diametermmφ 7.94
BodyNet dimensions (W х H х D)mm1240 x 495 x 200
Packing size (W х H х D)mm1345 x 595 x 300
Net weightkg26.5
Gross weightkg33.5
Pipe connectionsWater inlet/outlet pipeinchG3/4
Drain pipemmODφ18.5

Notes:

H: High fan speed; M: Medium fan speed; L: Low fan speed.

  1. Cooling conditions: Entering water 7°C, leaving water 12°c, Entering air temperature 27°C DB/l 9°C WB.
  2. Heating conditions: Entering water 45°C, leaving water 40°C, Entering air temperature 20°C DB/15°C WB.
Manufacturer Midea
Type Fan Coil
Indoor Unit MKH2-V500-R4
Power supply (V/ø/Hz) 230 / 1 / 50
Cooling Capacity (kW) 4.85
Heating Capacity (kW) 5.25
Power Input Cooling/Heating (kW) 0.052 / 0.052
Dimensions - Indoor Unit WxHxD (mm) 1240 x 495 x 200
Weight - Indoor Unit (kg) 26.5
No reviews