Technical Specifications for Three-phase DVM System Samsung AM080FXMDGH/EU | ||
---|---|---|
Model (outdoor unit) | AM080FXMDGH/EU | |
Power Supply | Φ/#/V/Hz | 3 / 4 / 380-415 / 50 |
HP | 8 | |
Capacity Cooling | kW | 22.40 |
Capacity Heating | kW | 25.00 |
Maximum number of connectable indoor units | ea | 13.0 |
Total capacity of the connected indoor units (Min./Max.) | kW | 11.20 / 29.10 |
Power Input Cooling | kW | 5.72 |
Power Input Heating | kW | 4.88 |
Current Input Cooling | A | 9.66 |
Current Input Heating | A | 8.24 |
Current (MCA) | A | 18.0 |
Current (MFA) | A | 25 |
EER1 Cooling | W/W | 3.92 |
COP1 Heating | W/W | 5.12 |
SEER1 | W/W | 9.22 |
Compressor (Type) | Inverter Scroll | |
Oil (Type) | PVE | |
Oil (Initial Charge) | cc | 2,800 |
Fan (Type) | Propeller / BLDC | |
Air Flow | m3/min | 135 |
External Static Pressure | Pa | 29.40 |
Liquid Pipe | ø, mm | 9.52 |
Gas Pipe | ø, mm | 19.05 |
Piping length (ODU-IDU) (Max.) | m | 100 |
Piping length (1st Branch-IDU) (Max.) | m | 40 |
Total piping length (System) (Max.) | m | 300 |
Level difference (IDU-IDU) (Max.) | m | 30 |
Refrigerant | R410A | |
Factory Charging | kg / tCO2e | 3.7 / 7.73 |
Sound Pressure2 (Cooling / Heating) | dB(A) | 56 / 58 |
Sound Power | dB(A) | 74 |
Weight | kg | 135 |
Dimensions (W x H x D) | mm | 940 x 1420 x 330 |
Operating Temperature (Cooling) | °C | -5 ~ 48 |
Operating Temperature (Heating) | °C | -20 ~ 24 |
Notes:
1Performances are based on the following test conditions:
2Sound pressure level is obtained in an anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. Sound pressure level may differ according to operating conditions. Sound power level is an absolute value that a sound source generates.
3ODU: Outdoor Unit,
IDU: Indoor Unit
Technical Specifications for Hydro Module Samsung AM250TNBFEB/EU | ||
---|---|---|
Model (indoor unit) | AM250TNBFEB/EU | |
Power Supply | Φ/#/V/Hz | 1Φ/2/220–240/50 |
Capacity Cooling | kW | - |
Capacity Heating | kW | 25 |
Power Input Cooling | kW | - |
Power Input Heating | kW | 5.0 |
Current Input Cooling | A | - |
Current Input Heating | A | 23.10 |
MCA (Including External Contact) | 30.0 | |
MFA | A | 40 |
Heat Exchanger Type | PHE | |
Heat Exchanger Quantity | 2 | |
Heat Exchanger Pipe Size | ø, inch | PT 1 (25A) |
Heat Exchanger Water Flow Rate | l/min | 36 |
Heat Exchanger Flow Switch | l/min | 12 |
Piping Connections Liquid | ø, mm | 9.52 |
ø, inch | 3/8 | |
Piping Connections Gas | ø, mm | 15.88 |
ø, inch | 5/8 | |
Refrigerant Type | R134a | |
Refrigerant Control Method | EEV | |
Sound Pressure | dB(A) | 42 |
Net Weight | kg | 105 |
Net Dimensions (W × H × D) | mm | 518 x 1210 x 330 |
Operating Temperature (Cooling) | ˚C | - |
Operating Temperature (Heating) | ˚C | -20 ~ 43 |
Hot Water (Main Cooling, HR) | ˚C | -20 ~ 43 |
Leaving Water (Cooling) | ˚C | - |
Leaving Water (Heating) | ˚C | 25 ~ 80 |
Manufacturer | Samsung |
Type | Central air conditioning |
Technology | Inverter |
Series | DVM S Eco Heat Recovery |
Outdoor Unit | AM080FXMDGH/EU |
Power supply (V/ø/Hz) | 380-415 / 3 / 50 |
Cooling Capacity (kW) | 22.40 |
Heating Capacity (kW) | 25.00 |
EER (Energy Efficiency in Cooling) | 3.92 |
COP (Energy Efficiency in Heating) | 5.12 |
Sound Pressure Outdoor Unit - Cooling/Heating dB(A) | 56 / 58 |
Sound Power Outdoor Unit - Cooling/Heating dB(A) | 74 / 74 |
Air Flow Outdoor Unit (m3/min) | 135 |
Dimensions - Outdoor Unit WxHxD (mm) | 940 x 1420 x 330 |
Weight - Outdoor Unit (kg) | 135 |
Piping Connections - Liquid/Gas (mm) | 9.52 / 19.05 |
Maximum Pipe Lenght (m) | 100 |
Maximum Height Difference Between Indoor Units (m) | 30 |
Operation Range - Cooling (°C) | -5 ~ 48 |
Operation Range - Heating (°C) | -20 ~ 24 |
Refrigerant | R410A |